AF2ZP0CE - ACE2 350/450 - User Manual Page - 7/83
3 SPECIFICATION FOR THE INPUT
DEVICES FILLING UP THE INSTALLATION
KIT
The ACE2 inverter needs some external parts in order to work. The following
devices complete the kit for the ACE2 installation.
3.1 Microswitches
- The microswitches must have a contact resistance lower than 0.1 and a
leakage current lower than 100 µA.
- When full load connected, the voltage drop between the key switch contacts
must be lower than 0.1 V.
- The microswitches send a voltage signal to the microprocessor when a
function request (for ex.: running request) is made.
3.2 Accelerator unit
The accelerator unit can consist of a potentiometer or an Hall effect device.
It should be in a 3-wire configuration. The potentiometer is supplied through
CNA#2.
Potentiometer output signal must be input to CPOT (CNA#3), signal range is
from 0 to 10 V.
The negative supply of the potentiometer has to be taken from CNA#9 (GND), or
from CNA-5 (REV/ 1ST SPEED) if the diagnosis PEDAL WIRE KO is done. In
this case the hardware must be configured closing a jumper on the logic card.
Potentiometer value should be in the 0.5 – 10 k range; generally, the load
should be in the 1.5 mA to 30 mA range. Faults can occur if it is outside this
range.
The standard connection for the potentiometer is the one in the Left side of next
figure (potentiometer on one end at rest) in combination with a couple of Travel
demand switches. On request it is also possible the handling in the Right side of
next figure (potentiometer in the middle at rest) still in combination with a couple
of Travel demand switches.
The Procedure for automatic potentiometer signal acquisition is carried out using
the Console. This enables adjustment of the minimum and maximum useful